TDV – Technische Daten

Model TDV 01 A TDV 02 A TDV 03 A TDV 04 A TDV 05 A TDV 06 A
Cooler version Dry Dry Dry Dry Dry Dry
Cooling capacity (1) [kW] 64 127 221 304 368 461
Nominal water flow (1) [m3/h] 6.0 12.0 20.8 28.6 34.0 42.6
Water pressure drop [bar] 0.2 0.2 0.2 0.4 0.2 1.3
Total air flow [m3/h] 24,780 48,330 75,340 100,830 126,330 149,110
Dimensions [mm] L(3)[5] [mm] 2150 (1975) 3056 (2881) 4206 (4031) 5690 (5432) 6850 (6582) 8076 (7750)
L(4)[5] [mm] 2445 (2270) 3595 (3420) 4715 (4431) 5940 (5756) 7090 (6906) 8254 (8064)
W [mm] 1715
H [mm] 2133
Model TDV 01 AD TDV 02 AD TDV 03 AD TDV 04 AD TDV 05 AD TDV 06 AD
Cooler version Adiabatic Adiabatic Adiabatic Adiabatic Adiabatic Adiabatic
Cooling capacity (1) [kW] 112 221 365 494 611 737
Nominal water flow (1) [m3/h] 11.0 21.0 34.0 46.3 57.0 63.5
Water pressure drop [bar] 0.6 0.5 0.5 1.0 0.5 2.7
Total air flow [m3/h] 22,000 44,000 66,000 88,000 110,000 132,000
Dimensions [mm] L(3)[5] [mm] 2150 (1975) 3056 (2881) 4206 (4031) 5690 (5432) 6850 (6582) 8076 (7750)
L(4)[5] [mm] 2445 (2270) 3595 (3420) 4715 (4431) 5940 (5756) 7090 (6906) 8254 (8064)
W [mm] 2115
H [mm] 2133
Total installed power (2) [kW] 2.30 4.30 6.30 8.30 10.30 12.30
Maximum absorbed current (2) [A] 4.20 8.40 12.60 16.80 21.00 25.20
Axial Fans Qty./Diam. [No./mm] 1/900 2/900 3/900 4/900 5/900 6/900
Water content [l] 64 94 209 258 316 359
Hydraulic connection – in/out 3″ 4
Fan control Phase cut or VSD
Controller ElektronikonTM MK5S + SMARTLINK
Power supply [V/Ph/Hz) 400/3+PE/50
Auxiliary voltage 24Vdc
Electrical approval IEC/cULus
Pressure vessel approval PED 2014/68/UE
(1) Reference condition: Ambient Air 35°C with RH=40%; Water in 50°C / out 40°C with/without pump; % Glycol=25%; Elevation above sea level=0
(2) Value specified for machine with „no pump“
(3) Overall dimensions without manifold
(4) Overall dimensions with manifold
(5) Value between brackets are referred to phase cut version variants