REFERENCE CONDITIONS |
|
|
|
|
|
|
|
|
Cooling power (kW) |
|
|
90 |
275 |
425 |
650 |
900 |
|
Compressor return water temperature (°C) |
|
|
90 |
90 |
90 |
90 |
90 |
|
Compressor supply water temperature (°C) |
|
|
40 |
40 |
40 |
40 |
40 |
|
Secondary water inlet temperature (°C) |
|
|
35 |
35 |
35 |
35 |
35 |
|
Secondary water temperature rise (°C) |
|
|
15 |
15 |
15 |
15 |
15 |
|
Compressor water flow (m³/h) |
|
|
1.6 |
4.8 |
7.4 |
11.3 |
15.6 |
|
Secondary water flow (m³/h) |
|
|
5.2 |
15.9 |
24.5 |
37.5 |
52 |
|
|
|
|
|
|
|
|
|
|
LIMITATIONS |
|
|
|
|
|
|
|
|
Maximum ambient temperature (°C) |
|
|
40 |
40 |
40 |
40 |
40 |
|
Maximum altitude (m) |
|
|
1000 |
1000 |
1000 |
1000 |
1000 |
|
Maximum secondary water inlet pressure (bar(g)) |
|
|
10 |
10 |
10 |
10 |
10 |
|
Maximum secondary water glycol (%) |
|
|
30 |
30 |
30 |
30 |
30 |
|
Maximum compressor water glycol (%) |
|
|
10 |
10 |
10 |
10 |
10 |
|
|
|
|
|
|
|
|
|
|
PERFORMANCE DATA |
|
|
|
|
|
|
|
|
Cooling power (kW) (90) |
|
|
|
|
|
|
|
|
|
Compressor return water temperature (°C) |
70 |
59 |
171 |
270 |
517 |
752 |
|
|
Compressor return water temperature (°C) |
80 |
86 |
248 |
405 |
650 |
900 |
|
|
Compressor return water temperature (°C) |
90 |
90 |
275 |
425 |
650 |
900 |
|
Mean sound pressure level (dB(A)) (18) |
|
|
58 |
58 |
64 |
70 |
75 |
|
|
|
|
|
|
|
|
|
|
DESIGN DATA |
|
|
|
|
|
|
|
|
Mass (kg) |
|
|
630 |
780 |
980 |
1190 |
1260 |
|
Canopy length (m) |
|
|
1.95 |
1.95 |
1.95 |
1.95 |
1.95 |
|
Canopy width (m) |
|
|
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
|
Canopy heigth (m) |
|
|
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |