Metric technical specs TDV 01-06 FP (phase-cut fans)/FV (VSD fans)

Dry cooler

Technical specifications TDV 01 A TDV 02 A TDV 03 A TDV 04 A TDV 05 A TDV 06 A
Cooling capacity (1) [kW] 64 127 221 304 368 461
Nominal water flow (1) [m3/h] 6.0 12.0 20.8 28.6 34.0 42.6
Total air flow [m3/h] 24,780 48,330 75,340 100,830 126,330 149,110
Dimensions [mm]
L(3)(5) [mm] 2150 (1975) 3056 (2881) 4206 (4031) 5690 (5432) 6850 (6582) 8076 (7750)
L(4)(5) [mm] 2445 (2270) 3595 (3420) 4715 (4431) 5940 (5756) 7090 (6906) 8254 (8064)
W [mm] 2.115
H [mm] 2.133

Adiabatic cooler

Technical specifications TDV 01 AD TDV 02 AD TDV 03 AD TDV 04 AD TDV 05 AD TDV 06 AD
Cooling capacity (1) [kW] 112 221 365 494 611 737
Nominal water flow (1) [m3/h] 11,0 21,0 34,0 46,3 57,0 63,5
Water pressure drop [bar] 0,6 0,5 0,5 1,0 0,5 2,7
Total air flow [m3/h] 22.000 44.000 66.000 88.000 110.000 132.000
Dimensions
L(3)(5)  [mm] 2150 (1975) 3056 (2881) 4206 (4031) 5690 (5432) 6850 (6582) 8076 (7750)
L(4)(5)[mm] 2445 (2270) 3595 (3420) 4715 (4431) 5940 (5756) 7090 (6906) 8254 (8064)
W [mm] 2.115
H [mm] 2.133
Total installed power (2) [kW] 2.30 4.30 6.30 8.30 10.30 12.30
Maximum absorbed current (2) [A] 4.20 8.40 12.60 16.80 21.00 25.20
Axial fans qty./diam. [no./mm] 1/900 2/900 3/900 4/900 5/900 6/900
Water content [l] 64 94 209 258 316 359
Hydraulic connection – in/out 3″ 4″
Fan control Phase cut or VSD
Controller ElektronikonTM MK5S
 + SMARTLINK
Power supply [V/Ph/Hz] 400/3+PE/50
Auxiliary voltage 24 Vdc
Electrical approval IEC/cULus
Pressure vessel approval PED 2014/68/UE

(1) Reference condition: Ambient Air 35°C with RH=40%; Water in 50°C / out 40°C with/without pump; % Glycol=25%; Elevation above sea level=0
(2) Value specified for machine with “no pump”
(3) Overall dimensions without manifold
(4) Overall dimensions with manifold
(5) Value between brackets are referred to phase cut version variants